Evaluation of heat transfer and exergy loss in a concentric double pipe exchanger equipped with helical wires

dc.contributor.authorAkpinar, Ebru Kavak
dc.date.accessioned2026-08-12T17:44:37Z
dc.date.issued2006
dc.departmentFırat Üniversitesi
dc.description.abstractIn this study, the effects on heat transfer, friction factor and dimensionless exergy loss were investigated experimentally by mounting helical (spring shaped) wires of different pitch in the inner pipe in a double pipe heat exchanger. In the experiments, hot (air) and cold (water) fluids flowed through the inner pipe and annulus, respectively. The experiments were performed for both parallel and counter current flow modes of the fluids at Reynolds numbers between 6500 and 13,000. An augmentation of up to 2.64 times in Nusselt number compared to the empty pipe was obtained in the helical system. The increase in friction factor was about 2.74 times that of the empty pipe, depending on Reynolds number and the pitch or helical number. An augmentation of up to 1.16 times in the dimensionless exergy loss compared to the empty pipe was obtained in the helical system. Some empirical correlations expressing the results were also derived and discussed. (c) 2006 Elsevier Ltd. All rights reserved.
dc.identifier.doi10.1016/j.enconman.2005.12.014
dc.identifier.endpage3486
dc.identifier.issn0196-8904
dc.identifier.issn1879-2227
dc.identifier.issue18-19
dc.identifier.orcid0000-0003-0666-9189
dc.identifier.scopus2-s2.0-33745893781
dc.identifier.scopusqualityQ1
dc.identifier.startpage3473
dc.identifier.urihttps://doi.org/10.1016/j.enconman.2005.12.014
dc.identifier.urihttps://hdl.handle.net/11508/60344
dc.identifier.volume47
dc.identifier.wosWOS:000239823900052
dc.identifier.wosqualityQ1
dc.indekslendigikaynakWeb of Science
dc.indekslendigikaynakScopus
dc.language.isoen
dc.publisherPergamon-Elsevier Science Ltd
dc.relation.ispartofEnergy Conversion and Management
dc.relation.publicationcategoryMakale - Uluslararası Hakemli Dergi - Kurum Öğretim Elemanı
dc.rightsinfo:eu-repo/semantics/closedAccess
dc.snmzKA_WoS_20260511
dc.subjectconcentric double pipe heat exchanger
dc.subjecthelical wires
dc.subjectheat transfer
dc.subjectexergy loss
dc.subjectfriction factor
dc.titleEvaluation of heat transfer and exergy loss in a concentric double pipe exchanger equipped with helical wires
dc.typeArticle

Dosyalar