Energetic performance analysis of a ground-source heat pump system with latent heat storage for a greenhouse heating

dc.contributor.authorBenli, Huseyin
dc.date.accessioned2026-08-12T17:46:25Z
dc.date.issued2011
dc.departmentFırat Üniversitesi
dc.description.abstractIn this study, a ground-source heat pump heating system with a latent heat thermal storage tank was designed while its thermal energy storage performance was investigated. The heating system mainly consists of a ground heat exchanger, a heat pump, a cylindrical latent heat thermal storage tank, measuring units and a heating space of model-sized glass greenhouses with 30 m(2), located in the greenhouse district of Firat University, Elazig, in Turkey. In the experiments, the performance characteristics of a ground-source heat pump greenhouse heating system with a 246 m horizontal 12.7 mm nominal diameter horizontal closed-loop ground heat exchanger and the use of phase change materials (PCM) for energy saving and management in greenhouses were investigated. The heating coefficient of performances of the ground-source heat pump (COP(HP)) and the overall system (COP(sys)) are obtained, to be in the range of 2.3-3.8 and 2-3.5 respectively. Although significant savings are possible with this heating system, a substantial investment in equipment and facilities may be required. The experiments results were obtained from October to May in heating seasons of 2005-2006. The results showed that the utilization of ground-source heat pump-PCM is suitable for greenhouse heating in this district. (C) 2010 Elsevier Ltd. All rights reserved.
dc.description.sponsorshipFirat University
dc.description.sponsorshipThe author gratefully acknowledge the financial support from the Firat University Research Fund. My sincere thanks are also for Mr. Mustafa Ceyhanli who is the founder and manager of the Ceylanlar Greenhouse for his invaluable support (Ceylanlar Greenhouse is a Turkish company based in Adana. Further information about the company is available at www.ceylanlar.com.tr).
dc.identifier.doi10.1016/j.enconman.2010.07.033
dc.identifier.endpage589
dc.identifier.issn0196-8904
dc.identifier.issue1
dc.identifier.orcid0000-0002-4057-8750
dc.identifier.scopus2-s2.0-80054746550
dc.identifier.scopusqualityQ1
dc.identifier.startpage581
dc.identifier.urihttps://doi.org/10.1016/j.enconman.2010.07.033
dc.identifier.urihttps://hdl.handle.net/11508/61059
dc.identifier.volume52
dc.identifier.wosWOS:000284746800069
dc.identifier.wosqualityQ1
dc.indekslendigikaynakWeb of Science
dc.indekslendigikaynakScopus
dc.language.isoen
dc.publisherPergamon-Elsevier Science Ltd
dc.relation.ispartofEnergy Conversion and Management
dc.relation.publicationcategoryMakale - Uluslararası Hakemli Dergi - Kurum Öğretim Elemanı
dc.rightsinfo:eu-repo/semantics/closedAccess
dc.snmzKA_WoS_20260511
dc.subjectGround-source heat pump (GSHP)
dc.subjectPhase change material (PCM)
dc.subjectRenewable energy
dc.titleEnergetic performance analysis of a ground-source heat pump system with latent heat storage for a greenhouse heating