Experimental thermal performance evaluation of a horizontal ground-source heat pump system

dc.contributor.authorInalli, M
dc.contributor.authorEsen, H
dc.date.accessioned2026-08-12T17:44:29Z
dc.date.issued2004
dc.departmentFırat Üniversitesi
dc.description.abstractThe goal of the present study is to validate the effects of the parameters such as the buried depth of earth coupled heat exchanger, mass flow rate of the water-antifreeze solution and sewer water on the performance of a horizontal ground-source heat pump (GSHP) system used for space heating experimentally. The GSHP system connected to a test room with 16.24 m(2) floor area in Firat University, Elazig (38.41degreesN, 39.14degreesE), Turkey, was designed and constructed. The heating and cooling loads of the test room were 2.5 and 3.1 kW at design conditions, respectively. The experimental results were obtained from November to April in heating season of 2002-2003. The average performance coefficients of the system (COPsys) for horizontal ground heat exchanger in the different trenches, at 1 and 2 m depths, were obtained to be 2.66 and 2.81, respectively. Results obtained from experimental measurement concluded that the horizontal GSHP systems can be used for Elazig, Turkey climatic conditions. (C) 2004 Elsevier Ltd. All rights reserved.
dc.identifier.doi10.1016/j.applthermaleng.2004.01.005
dc.identifier.endpage2232
dc.identifier.issn1359-4311
dc.identifier.issn1873-5606
dc.identifier.issue14-15
dc.identifier.orcid0000-0002-6260-4948
dc.identifier.orcid0000-0001-8802-8080
dc.identifier.scopus2-s2.0-3142645475
dc.identifier.scopusqualityQ1
dc.identifier.startpage2219
dc.identifier.urihttps://doi.org/10.1016/j.applthermaleng.2004.01.005
dc.identifier.urihttps://hdl.handle.net/11508/60284
dc.identifier.volume24
dc.identifier.wosWOS:000223901000018
dc.identifier.wosqualityQ1
dc.indekslendigikaynakWeb of Science
dc.indekslendigikaynakScopus
dc.language.isoen
dc.publisherPergamon-Elsevier Science Ltd
dc.relation.ispartofApplied Thermal Engineering
dc.relation.publicationcategoryMakale - Uluslararası Hakemli Dergi - Kurum Öğretim Elemanı
dc.rightsinfo:eu-repo/semantics/closedAccess
dc.snmzKA_WoS_20260511
dc.subjectground-source heat pump
dc.subjecthorizontal heat exchanger
dc.subjectsewer water
dc.subjectcoefficient of performance (COPsys)
dc.subjectspace heating
dc.titleExperimental thermal performance evaluation of a horizontal ground-source heat pump system