Experimental Analysis of Different Refrigerants' Thermal Behavior and Predicting Their Performance Parameters

dc.contributor.authorPektezel, Oguzhan
dc.contributor.authorDas, Mehmet
dc.contributor.authorIbrahim Acar, Halil
dc.date.accessioned2026-08-12T17:20:50Z
dc.date.issued2023
dc.departmentFırat Üniversitesi
dc.description.abstractThis study experimentally compares thermodynamic performance of R290 and R404A refrigerants in a refrigeration system. In the first part of the paper, energy analysis of the refrigeration system was performed at various evaporator and condenser temperatures. Results revealed that R404A refrigerant caused an 18.6% increase in compressor power consumption. The highest coefficient of performance values in the system for R290 and R404A were 3.99 and 3.21, respectively. The second part of the paper includes artificial intelligence prediction studies. The pace and elastic net regression models were used to predict performance parameters. A single equation that can predict the cooling capacity and compressor power consumption of R290 and R404A simultaneously was derived. For the cooling capacity, pace regression showed mean absolute error of 0.0252 and root-mean-squared error of 0.0334, while elastic net regression indicated mean absolute error of 0.1103 and root-mean-squared error of 0.1262. It was concluded that R290 had better thermodynamic performance than R404A and the equations obtained with artificial intelligence were applicable to predict the experimental findings, regardless of which refrigerant gas was used.
dc.description.sponsorshipTokat Gaziosmanpasa University Scientific Research Projects Office [2020/122]
dc.description.sponsorshipThe authors would like to thank Tokat Gaziosmanpasa University Scientific Research Projects Office for supporting this study with the project number of 2020/122.
dc.identifier.doi10.2514/1.T6660
dc.identifier.endpage319
dc.identifier.issn0887-8722
dc.identifier.issn1533-6808
dc.identifier.issue2
dc.identifier.scopus2-s2.0-85153752130
dc.identifier.scopusqualityQ2
dc.identifier.startpage309
dc.identifier.urihttps://doi.org/10.2514/1.T6660
dc.identifier.urihttps://hdl.handle.net/11508/53718
dc.identifier.volume37
dc.identifier.wosWOS:000890465200001
dc.identifier.wosqualityQ3
dc.indekslendigikaynakWeb of Science
dc.indekslendigikaynakScopus
dc.language.isoen
dc.publisherAmer Inst Aeronautics Astronautics
dc.relation.ispartofJournal of Thermophysics and Heat Transfer
dc.relation.publicationcategoryMakale - Uluslararası Hakemli Dergi - Kurum Öğretim Elemanı
dc.rightsinfo:eu-repo/semantics/closedAccess
dc.snmzKA_WoS_20260511
dc.subjectLow Gwp Mixtures
dc.subjectR404A
dc.subjectR134A
dc.subjectR450A
dc.subjectReplacement
dc.subjectR600A
dc.subjectR454C
dc.titleExperimental Analysis of Different Refrigerants' Thermal Behavior and Predicting Their Performance Parameters