dc.description.abstractDistribution Static Compensator (D-STATCOM) is a shunt compensation device used to improve electric power quality in distribution systems. It is well-known that D-STATCOM is a nonlinear, semi-defined and time-varying system. Therefore, control of D-STATCOM by the conventional control techniques is very difficult task. In this paper, the control of D-STATCOM is carried out by the neuro-fuzzy controller (NFC) which has non-linear and robust structure. For this aim, an experimental setup based on three-level H-bridge inverter is constructed. Phase angle control method is used for control of D-STATCOM's output reactive power. Control algorithm for this experimental setup is prepared in MATLAB/Simulink and downloaded to DS1103 controller card. A Mamdani type NFC is designed for control of D-STATCOM's reactive current. Output of NFC is integrated to increase tracking performance of controller in steady state. The performance of D-STATCOM is experimentally evaluated by changing reference reactive current as on-line. The experimental results show that the proposed controller gives very satisfactory performance under different loading conditions.
dc.description.sponsorshipScientific and Technology Research Council of Turkey (TUBITAK) [107E245]
dc.description.sponsorshipThis work was supported by Scientific and Technology Research Council of Turkey (TUBITAK) with 107E245 numbered project.
dc.identifier.doi10.4316/AECE.2012.01013
dc.identifier.endpage84
dc.identifier.issn1582-7445
dc.identifier.issn1844-7600
dc.identifier.issue1
dc.identifier.orcid0000-0003-1100-6179
dc.identifier.orcid0000-0002-7365-4318
dc.identifier.orcid0000-0002-7435-0906
dc.identifier.orcid0000-0002-9048-6547
dc.identifier.orcid0000-0003-1100-6179
dc.identifier.scopus2-s2.0-84860724702
dc.identifier.scopusqualityQ3
dc.identifier.startpage77
dc.identifier.urihttps://doi.org/10.4316/AECE.2012.01013
dc.identifier.urihttps://hdl.handle.net/11508/48443
dc.identifier.volume12
dc.identifier.wosWOS:000301075000013
dc.identifier.wosqualityQ4
dc.indekslendigikaynakWeb of Science
dc.indekslendigikaynakScopus
dc.language.isoen
dc.publisherUniv Suceava, Fac Electrical Eng
dc.relation.ispartofAdvances in Electrical and Computer Engineering
dc.relation.publicationcategoryMakale - Uluslararası Hakemli Dergi - Kurum Öğretim Elemanı
dc.rightsinfo:eu-repo/semantics/openAccess
dc.snmzKA_WoS_20260511
dc.subjectelectric power quality
dc.subjectD-STATCOM
dc.subjectthree-level H-bridge inverter
dc.subjectneuro-fuzzy controller
dc.subjectMATLAB
dc.titlePhase Angle Control of Three Level Inverter Based D-STATCOM Using Neuro-Fuzzy Controller
dc.typeArticle

Dosyalar