Seasonal cooling performance of a ground-coupled heat pump system in a hot and and climate

dc.contributor.authorInalli, M
dc.contributor.authorEsen, H
dc.date.accessioned2026-08-12T17:43:27Z
dc.date.issued2005
dc.departmentFırat Üniversitesi
dc.description.abstractThe goal of the present study is to validate the cooling performance of a ground-coupled heat pump system established in Firat University, Elazig (38.41 degrees N, 39.14 degrees E), Turkey. The cooling load of the test room was 3.1 kW at design conditions. The experimental results were obtained from June to September in cooling season of 2003. The ground heat exchanger was used, and it was buried with in 2 m depth trench. The average cooling performance coefficient of the system (COPoverall) was obtained to be 2.01. The results obtained from experimental measurement showed that these systems could be used safely, reliably and efficiently at the lowest possible cost for Elazig, Turkey climatic conditions. Especially, the seasonal energy efficiency ratio (SEER) of this system is moderate at longer-term testing. (c) 2004 Elsevier Ltd. All rights reserved.
dc.identifier.doi10.1016/j.renene.2004.10.015
dc.identifier.endpage1424
dc.identifier.issn0960-1481
dc.identifier.issn1879-0682
dc.identifier.issue9
dc.identifier.orcid0000-0001-8802-8080
dc.identifier.orcid0000-0002-6260-4948
dc.identifier.scopus2-s2.0-14644426526
dc.identifier.scopusqualityQ1
dc.identifier.startpage1411
dc.identifier.urihttps://doi.org/10.1016/j.renene.2004.10.015
dc.identifier.urihttps://hdl.handle.net/11508/60141
dc.identifier.volume30
dc.identifier.wosWOS:000228775600008
dc.identifier.wosqualityQ1
dc.indekslendigikaynakWeb of Science
dc.indekslendigikaynakScopus
dc.language.isoen
dc.publisherPergamon-Elsevier Science Ltd
dc.relation.ispartofRenewable Energy
dc.relation.publicationcategoryMakale - Uluslararası Hakemli Dergi - Kurum Öğretim Elemanı
dc.rightsinfo:eu-repo/semantics/closedAccess
dc.snmzKA_WoS_20260511
dc.subjectground-coupled heat pump
dc.subjectspace cooling
dc.subjecthorizontal heat exchanger
dc.subjectcoefficient of performance
dc.titleSeasonal cooling performance of a ground-coupled heat pump system in a hot and and climate
dc.typeArticle

Dosyalar