dc.description.abstractSurge response of the transmission tower in a three-phase transmission system is computed using s-domain nonuniform single-phase transmission line modelling. First, tower top voltage is obtained considering the tower and the ground wire by excluding the effect of the phase conductors, and then the induced voltages on the phase conductors as a result of the current flowing through the ground wire are computed using the magnetic coupling between the ground wire and the phase conductors. The first step of the analysis is the formulation of the system response in the s-domain, and the second step is the frequency to time domain conversion, which is carried out using fast inverse Laplace transform (FILT). The voltages on the phase conductors and the voltages across the tower insulators are computed, and some of the results obtained using s-domain analysis are compared with those obtaining using electromagnetic transients program (EMTP). The effect of frequency dependence of the line parameters is investigated.
dc.identifier.doi10.1007/s00202-004-0246-2
dc.identifier.endpage259
dc.identifier.issn0948-7921
dc.identifier.issn1432-0487
dc.identifier.issue5
dc.identifier.orcid0000-0003-2905-1816
dc.identifier.orcid0000-0002-6562-0839
dc.identifier.scopus2-s2.0-23744465240
dc.identifier.scopusqualityQ1
dc.identifier.startpage253
dc.identifier.urihttps://doi.org/10.1007/s00202-004-0246-2
dc.identifier.urihttps://hdl.handle.net/11508/51305
dc.identifier.volume87
dc.identifier.wosWOS:000230516100005
dc.identifier.wosqualityQ3
dc.indekslendigikaynakWeb of Science
dc.indekslendigikaynakScopus
dc.language.isoen
dc.publisherSpringer
dc.relation.ispartofElectrical Engineering
dc.relation.publicationcategoryMakale - Uluslararası Hakemli Dergi - Kurum Öğretim Elemanı
dc.rightsinfo:eu-repo/semantics/closedAccess
dc.snmzKA_WoS_20260511
dc.subjectlightning surge
dc.subjectnonuniform line
dc.subjects-domain analysis
dc.subjecttransmission tower
dc.subjectEMTP
dc.titles-domain analysis of lightning surges in three-phase systems using nonuniform single-phase line model
dc.typeArticle

Dosyalar