Performance assessment of a polyclinic heating and cooling system in a hospital building

dc.contributor.authorKarakasli, Evren
dc.contributor.authorÖztop, Hakan Fehmi
dc.contributor.authorHepbasli, Arif
dc.date.accessioned2026-08-12T17:04:38Z
dc.date.issued2016
dc.departmentFırat Üniversitesi
dc.description.abstractThe performance of a hospital building, heated by a natural gas-fired boiler system, was assessed by using energy and exergy analysis methods in this study. The analysis was performed from the primary energy production to the envelope of the building. In the evaluation, other parameters, such as total exergy input rate per area, total exergy input rate per volume and exergy flexibility factor were also utilised. It is found that overall energy and exergy efficiencies of the heating and cooling system were 13.4% and 1.35%, respectively. It may be concluded that in establishing energy policies, the exergy phenomenon should also be included because exergy is considered as a very useful and effective tool for buildings.
dc.identifier.doi10.1504/IJEX.2016.078513
dc.identifier.endpage86
dc.identifier.issn1742-8297
dc.identifier.issn1742-8300
dc.identifier.issue1
dc.identifier.scopus2-s2.0-84983591277
dc.identifier.scopusqualityQ3
dc.identifier.startpage70
dc.identifier.urihttps://doi.org/10.1504/IJEX.2016.078513
dc.identifier.urihttps://hdl.handle.net/11508/48802
dc.identifier.volume21
dc.identifier.wosWOS:000393194800004
dc.identifier.wosqualityQ4
dc.indekslendigikaynakWeb of Science
dc.indekslendigikaynakScopus
dc.language.isoen
dc.publisherInderscience Enterprises Ltd
dc.relation.ispartofInternational Journal of Exergy
dc.relation.publicationcategoryMakale - Uluslararası Hakemli Dergi - Kurum Öğretim Elemanı
dc.rightsinfo:eu-repo/semantics/closedAccess
dc.snmzKA_WoS_20260511
dc.subjectbuilding
dc.subjectenergy and exergy analysis
dc.subjectenergy conversion
dc.titlePerformance assessment of a polyclinic heating and cooling system in a hospital building